Junction Box Sizing Calculator (NEC 314.28)

Construction & Home Improvement

Calculate the minimum junction box dimension for a straight or angle conduit pull, per NEC Article 314.28.

Ad · Billboard
0.25 in12 in
0 in48 in

Minimum Box Dimension

16.000

Minimum required junction box length (straight pull) or distance to the opposite wall (angle pull), per NEC 314.28.

Share result
Reload calculator
Clear inputs

Found this calculator useful?

From Scratch To $10K/Month In 60 Days

This is a proven money making system that takes students by the hand to make at least $10,000 per month, every month. Students get 12 weeks of guided coaching in addition to the "MPS Super Funnel" and tools.

We value your privacy and promise not to sell or misuse your information. Here's our privacy policy.

Calculator Stats

Odeh Ahwal

Creators

Odeh Ahwal
Reviewed and verifiedThis calculator was reviewed and verified by the Calcupedia due diligence team.

0people find this calculator helpful

Views

Helpful

Saved

Embeds

Like
Share
Embed this calculator
Cite
Save
Ad · 300×250
Ad · 300×250

Frequently Asked Questions

What is the difference between a straight pull and an angle pull?

A straight pull is where a conduit enters and exits the box in the same direction, on opposite walls. An angle pull, or U pull, is where the conduit changes direction inside the box, or enters and exits the same wall. Angle pulls need more room to protect the conductor from a sharp bend, so they use a different, larger formula.

How is the minimum dimension calculated?

For a straight pull, the minimum length is 8 times the trade size of the largest conduit entering that wall. For an angle pull, the minimum distance to the opposite wall is 6 times the trade size of the largest conduit in that row, plus the sum of the trade sizes of all other conduits in the same row.

Is this the complete NEC 314.28 requirement?

This covers the core straight-pull and angle-pull minimum dimension formulas, the most commonly needed calculation. NEC 314.28 also includes additional rules for box depth with multiple rows of conduit, and Table 312.6(A) provides alternate values for conductors instead of conduit trade size. For a complex or unusual pull configuration, consult the full code text or a licensed electrician.

Spot a mistake? Tell us what's wrong.

Don't see what you need?

Request a calculator. The most-requested ones get built first in our monthly batch.

Request a calculator

Want this calculator on your website?

Embed the Junction Box Sizing Calculator (NEC 314.28) on any site — no code needed. Customize colors, remove branding, and track usage.

Embed it free →
Embed on any platform — Next.js, React, Vue.js, PHP, Laravel, Shopify, Wix, Webflow, Squarespace, and more